- 1 - TOHO ELECTRONICS INC. Program Controller TTM-339 Operation Manual Thank you for purchasing Toho Electronics’ TTM-339 series. Befo
- 10 - 4.8 Time signal output At starting each step, the time signals 1 to 4 are turned on upon elapse of the time set on the ON delay timer.
- 11 - The step changes when the external contact open (OFF) changes to the external contact closed (ON) during a program run. 4.11.4 Patter
- 12 - 4.13.2 Operation amount current limiter The operation amount and current value are limited at each point obtained by dividing SLL to SLH i
- 13 - Example: Assume the following for various settings and PV: PV = 120 C, operation amount limiter point 2 = 75.0%, current value limiter poi
- 14 - 4.14.3-2 Primary/secondary control operation amount increase time Setting items: Primary/secondary control operation amount increase time
- 15 - 4.16 PV filter setting 4.16.1 PV filter setting This setting is a function to achieve the CR filter effect on the software by performin
- 16 - 4.17 Event alarm By setting the events 1 to 4 function setting, outputs of EV 1 to 4 are turned on if PV is located within the alarm range
- 17 - 4.20 Electric Power Outage Function Upon recovery of the electric power after its outage during a run, the status at the time of the ou
- 18 - 5. Flow of Mode Change Operation and Run Operation 5.1Primary Power Source in the OFF status5.2Initial modePrimary power source ON5.3Norm
- 19 - Flow of the program setting mode Pattern No. setting modeMODE keyStep 1 temperature settingStep 1 time settingStep 2 temperature settingSt
- 2 - 1.Precautions on the use of the products Ensure to read this manual before using the equipment. Take care to understand the following for th
- 20 - Flow of the Common parameter setting mode Normal mode△ keyMODE keyMODE keyMODE keyMODE key: 3 secondsMODE keyMODE keyMODE keyMODE keyMODE k
- 21 - 5.1 List of settings in the pattern No. setting and program setting modes Name Setting content Initial value 1 SV * Setting temperature
- 22 - 5.5 Common parameter setting mode SET 4 (1) SET04 Name Setting content Initial value 1 SLH SV limiter upper limit (*2) (*3) Thermo
- 23 - 5.5 Common parameter setting mode SET 4 (2) SET04 Name Setting content Initial value 31 MV2 Secondary control operating amount 0.
- 24 - 5.6 Common parameter setting mode SET 5 to 8 SET05 to SET08 Name Setting content Initial value 1 E*F1 Event function 1 setting Fun
- 25 - 5.7 Common parameter setting mode SET 9 (2) SET09 Name Setting content Initial value With the selection of [MLF = 2,3], the followi
- 26 - 5.8 Common parameter setting mode SET 10 SET10 Name Setting content Initial value 1 INP1 Input type setting (*2) (*3) 0 K thermocoup
- 27 - 5.10 Common parameter setting mode SET 12 SET12 Name Setting content Initial value 1 PRT Communication protocol setting Press the MO
- 28 - 5.12 List of the alarm temperature setting mode setting Name Setting content Initial value 1 E1H Event 1 upper limit setting See
- 29 - 7. List of models TTM-339-□ □-□□□□□□ ① ② ③ Symbol Item Description Size 96 x
- 3 - Turn off the power supply before cleaning the equipment, and wipe it with a soft dry cloth. Do not use thinners, as they may cause defor
- 30 - Display/ Setting Display type LCD lamp red 15 pcs RUN,OUT,EV1,EV2,EV3,EV4、TS1,TS2,TS3,TS4,TIME,AUTO,MANU,AT,END LCD lamp
- 31 - 9.MAINTENANCE AND INSPECTIONS If any of the troubles still exists after following the above instruction, or for any other cases, contact ou
- 32 - TOHO ELECTRONICS INC. WEB.site http://www.toho-inc.com E-mail [email protected] Head of
- 4 - 2. Parts indication and Installation 2.1 Full panel face 2.2 Segment display section No. Segment character C
- 5 - 2.4 Lamp display section Lamp character Content PTN Lights up while a pattern in display. STP Lights up while a step in display. RU
- 6 - 2.7 Precautions on installation Warning Ensure to turn the power supply off before beginning removal or reinstallation of the equipment in
- 7 - 3. Terminal connection diagram Power supply 100 to 240 VAC ① X A Communications RS-485 ⑬ EV4 Open collector output ② B ⑭ TS1 Not in
- 8 - The use of shielded wires is recommended. For Pt100 (resistance temperature detector), use identical wires of low lead resistance and no
- 9 - 4.4 Wait function For the current step transferring to the next step, the next step does not begin if PV has not reached the wait zone (si