- 21 -
5.1 List of settings in the pattern No. setting and program setting modes
Name
Setting content
Initial value
1
SV *
Setting temperature (*1)
- (Termination of a run); SLL to SLH
0
2
W *
Wait function setting (*1)
0 to 4 (0 stands for no function)
0
3
TS1 *
Time signal 1 function setting (*1)
0 to 5 (0 stands for no function and 5 for in-a-selection step ON)
0
4
TS2 *
Time signal 2 function setting (*1)
0 to 5 (0 stands for no function and 5 for in-a-selection step ON)
0
5
TS3 *
Time signal 3 function setting (*1)
0 to 5 (0 stands for no function and 5 for in-a-selection step ON)
0
6
TS4 *
Time signal 4 function setting (*1)
0 to 5 (0 stands for no function and 5 for in-a-selection step ON)
0
7
ML *
Operation amount limiter function setting (*1)
0 to 4 (0 stands for no function)
0
8
T *
Setting time (*1)
0:00 to 99:59 (hour: minute); ~ (endless setting)
00:00
9
RNC
running times
0 - 99 times (0 for infinite number)
1
10
E ON
End signal ON time
0:00 to 99:59 (hour: minute); ~ (ON hold)
00:00
5.2 Common parameter setting mode SET 1
SET01
Name
Setting content
Initial value
1
PAT
Number-of-patterns setting (*2) (*3)
1 to 15 (pattern)
1
2
PVSV
PV start/SV start selection (*2)
PV
PV start
PV
SV
SV start
3
SVSV
Start temperature setting at SV start (*2)
Thermocouple/RTD input SLL to SLH (C)
0
Current/voltage input SLL to SLH (digit)
4
RNES
In-a-run output/end signal output selection
(*2)
0
In-a-run output
0
1
End signal output
5
ERUN
External drive signal selection (*2)
OFF
Internal run
OFF
ON
External run
6
TPV
Power outage restoration temperature width
setting
Thermocouple/RTD input 0.0 to 2999.9 (C) or 0 to 2999 (C)
0
Current/voltage input 0 to 29999 (digit)
5.3 Common parameter setting mode SET 2
SET02
Name
Setting content
Initial value
* Below, 1 and 2 are for the wait function setting, i.e., effective when 1 is selected.
1
WZ1
Wait zone 1 setting
Thermocouple/RTD input 0.0 to 999.9 (C) or 0 to 999 (C)
0
Current/voltage input 0 to 9999 (digit)
2
WT1
Wait time 1 setting
0:00 to 99:59 (hour: minute)
00:00
* Below, 3 and 4 are for the wait function setting, i.e., effective when 2 is selected.
3
WZ2
Wait zone 2 setting
same as Wait zone 1
0
4
WT2
Wait time 2 setting
00:00
* Below, 5 and 6 are for the wait function setting, i.e., effective when 3 is selected.
5
WZ3
Wait zone 3 setting
same as Wait zone 1
0
6
WZ3
Wait time 3 setting
00:00
* Below, 7 and 8 are for the wait function setting, i.e., effective when 4 is selected.
7
WZ4
Wait zone 4 setting
same as Wait zone 1
0
8
WT4
Wait time 4 setting
00:00
5.4 Common parameter setting mode SET 3
SET03
Name
Setting content
Initial value
* Below, 1 and 2 are for the time signal function setting, i.e., effective when 1 is selected.
1
ONT1
Time signal ON delay timer 1
0:00 to 99:59 (hours:minutes)
00:00
2
OFT1
Time signal OFF delay timer 1
0:00 to 99:59 (hours:minutes)
00:00
* Below, 3 and 4 are for the time signal function setting, i.e., effective when 2 is selected.
3
ONT2
Time signal ON delay timer 2
0:00 to 99:59 (hours:minutes)
00:00
4
OFT2
Time signal OFF delay timer 2
0:00 to 99:59 (hours:minutes)
00:00
* Below, 5 and 6 are for the time signal function setting, i.e., effective when 3 is selected.
5
ONT3
Time signal ON delay timer 3
0:00 to 99:59 (hours:minutes)
00:00
6
OFT3
Time signal OFF delay timer 3
0:00 to 99:59 (hours:minutes)
00:00
* Below, 7 and 8 are for the time signal function setting, i.e., effective when 4 is selected.
7
ONT4
Time signal ON delay timer 4
0:00 to 99:59 (hours:minutes)
00:00
8
OFT4
Time signal OFF delay timer 4
0:00 to 99:59 (hours:minutes)
00:00
Vista de página 20