5.10 Common parameter setting mode SET 12
SET12
Name
Setting content
Initial value
1
PRT
Communication protocol setting
Press the MODE key for making a setting effective.
0
0
TOHO protocol
1
MODBUS protocol (RTU mode)
2
MODBUS protocol (ASCII mode)
2
COM
Communication parameter
***1
1 bit
B8N2
***2
2 bits
**N*
None
**O*
Odd No.
**E*
Even No.
*7**
7 bits For MODBUS(RTU) setting, 7bits is ineffective
*8**
8 bits
N***
Nonexistent (settable for TOHO protocol)
B***
Existent (settable for TOHO protocol)
3
BPS
Communication speed setting
2.4
2400 bps
9.6
4.8
4800 bps
9.6
9600 bps
19.2
19200 bps
38.4
38400 bps
4
ADR
Communication address setting
TOHO protocol
1 to 99 (stations)
1
MODBUS protocol
1 to 247 (stations)
5
AWT
Communication response delay time setting
0 to 250 (ms)
0
6
MOD
Communication switchover setting
0
Write inhibit
1
Writable
1
7
SLV
Number-of-sub-controller-connections setting (*2)
0 to 10 (unit)
0
5.11 Common parameter setting mode SET 13
SET13
Name
Setting content
Initial value
1
LOC-1
Normal screen lock setting
During the lock ON, an attempt of changing a
setting results in LOC displayed on the screen.
0
2
LOC-2
Pattern No. setting mode lock setting
3
LOC-3
Alarm temperature setting mode lock setting
0
Lock turned off
4
LOC-4
PID setting mode lock setting
1
Lock turned on
5
LOC01
Common parameter setting mode SET01 lock setting
6
LOC02
Common parameter setting mode SET02 lock setting
7
LOC03
Common parameter setting mode SET03 lock setting
8
LOC04
Common parameter setting mode SET04 lock setting
9
LOC05
Common parameter setting mode SET05 lock setting
10
LOC06
Common parameter setting mode SET06 lock setting
11
LOC07
Common parameter setting mode SET07 lock setting
12
LOC08
Common parameter setting mode SET08 lock setting
13
LOC09
Common parameter setting mode SET09 lock setting
14
LOC10
Common parameter setting mode SET10 lock setting
15
LOC11
Common parameter setting mode SET11 lock setting
16
LOC12
Common parameter setting mode SET12 lock setting
17
LOCS1
Setting temperature (All steps in a batch)
18
LOCS2
Wait function setting (All steps in a batch)
19
LOCS3
Time signal 1 function setting (All steps in a batch)
20
LOCS4
Time signal 2 function setting (All steps in a batch)
21
LOCS5
Time signal 3 function setting (All steps in a batch)
22
LOCS6
Time signal 4 function setting (All steps in a batch)
23
LOCS7
Operation amount limiter function setting (All steps in a batch)
24
LOCS8
Setting time (All steps in a batch)
25
LOCS9
Run times
26
LOCSA
End signal ON time