48-7009-E 6-24
Primary control soft-start output setting
SEt04
CNt
Setting content
Initial value
26
SFM
ML 1 to MH 1 (%)
100.0
Set the primary control soft-start output setting.
A limit is set in a particular time period (or the primary control soft-start time) on the operating amount calculated.
Primary control soft-start time setting
SEt04
CNt
Setting content
Initial value
27
SFt
00:00 to 499:59 (minute seconds)
000:00
Soft-starting PID control
Primary control soft-
start output setting
Power-on
Operating amount
(%)
Time elapsed
Note
(1) The SOFT START operates both when the power is switched ON and when the Control Mode is
switched from "READY to RUN".
The switching of the Control Mode can be done with setting such as SEt04 Md)(SEt03 FU* and
SEt13 DIF
(2) Soft-start is effective only during equipment operation. Note that the time elapses even after the mode changes to
control stop, manual or AT.
(3) The set time can be changed during soft-start, where the set time is the time from power-on.
Example 1) When the set time is changed from 6 minutes to 4 minutes in 5 minutes after power-on, soft-start
immediately stops.
Example 2) When the set time is changed from 6 minutes to 8 minutes in 5 minutes after power-on, soft-start will stop
in 3 minutes.