Toho-electronics TTM200 Manual do Utilizador Página 122

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 121
48-7009-E 5-52
5.5.3 SET 21 program function setting screen
The program function setting screen is shown below.
SET21
PGF
PGMD
0
H/MP
0
WAIT
2
POC
0
25
25
Returns to SET21 PGF
SET01
INP1
C/P
0
PV value (present value)
SV value (setting value)
Hold MODE key pressed for 2 seconds
Input 1 setting screen
Press the key or key several times.
Program function setting mode
Press MODE key.
Operating type setting
Hold MODE key pressed for 2 seconds
No.
Setting range
0
Program mode 1 (without power failure compensation)
initial value
1
Program mode 2 (without power failure compensation)
2
Program mode 1 (with power failure compensation)
3
Program mode 2 (with power failure compensation)
* No display when C/P 0 (normal)
No.
Setting range
0
Constant value run mode (initial value)
1
Program run mode
Press MODE key.
Program mode setting
Press MODE key.
Power failure compensation range setting
Temperature input (initial value = 0)
0 to 999 (0.0 to 999.9) (C)
Analog input (initial value = 0)
0 to 9999 (digit)
* No display when C/P 0 (normal) or PGMd 0 or 1
(program run without power failure compensation)
Press MODE key.
Time unit setting
0
Hour: minute (step time) (initial value)
1
Hour: minute (soak time 1)
2
Hour: minute (soak time 2)
3
Minute: second (step time)
4
Minute: second (soak time 1)
5
Minute: second (soak time 2)
* No display when C/P 0 (normal)
Press MODE key.
WAIT range setting
Press MODE key.
Temperature input (initial value = 2)
Soak time 1: 0 to 999 (0.0 to 999.9) (C)
Soak time 2: 0 to 999 (0.0 to 999.9) (C)
Analog input
Soak time 1: 0 to 9999 (digit)
Soak time 2: 0 to 9999 (digit)
* No display when C/P 0 (normal) or H/MP 0 or 3
(step time)
Vista de página 121
1 2 ... 117 118 119 120 121 122 123 124 125 126 127 ... 263 264

Comentários a estes Manuais