Toho-electronics TTM-P9 Manual do Utilizador Página 13

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 16
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 12
12
From reset mode
Hold the key and the PATT./STEP
key down simultaneously.
Set an alarm output lower limit.
Set an alarm output upper limit.
Press the PATT./STEP key.
PV
"<::
SV
,
PV
"<:;
SV
Press the PATT./STEP key.
PID setting mode (The SET lamp lights.)
- This mode will set the PID constant (only during operation).
6.2 Parameter description
Program setting mode parameters
Character Description Initial value Setting range
*+
Set a step temperature 0 Setting range (K: 0 to 1200 °C/J: 0 to 800°C/R: 0 to 1300°C
-
Set a step time 0.00 0 to 99 hours 59 minutes
Common parameter setting mode parameters
Character Description Initial value Setting range
"#+*
Set the PV correction zero
point
0 -199 to +199°C
"#+6
Set the PV correction gain 1.00 0.50 to 2.00 times
"8(-
Forward/reverse
switchover
2 1: Forward action (cooling)/2: reverse action (heating)
"
9(
Sensor switchover 1 1: K thermocouple/2: J thermocouple/3: R thermocouple
"*:;
SV limiter upper limit 1200 SLL + 50°C to setting range upper limit
"*::
SV limiter lower limit 0 0°C to SLH-50°C
"#<-
Set the number of patterns 8 1 to 15 patterns
#+*+
Select PV/SV start PV PV: PV start/SV: SV start
*+*+
Set an SV start
temperature
0 Lower limit to upper limit of the temperature setting range
"
-
Proportional period R (relay output): 20
S (SSR output): 2
1 to 120 seconds
"
=>
Wait zone 0 0 to 100°C
"
=-
Wait time 0.00 0 to 99 hours 59 minutes
"<:?
Time signal/alarm output
type
00
(time signal)
0: Nil (time signal)
1: Deviation upper and lower limit
2: Deviation upper limit
3: Deviation lower limit
4: Deviation upper and lower limit
range
5: Absolute value upper and lower
limit
6: Absolute value upper limit
7: Absolute value lower limit
8: Absolute value upper and lower
limit range
0: No additional functions
1: Output held
2: Standby sequence
3: Output held + standby
sequence
"<:-
Alarm output sensitivity 1 0 to 199°C
-*@(
Time signal ON time 0.00 0 to 99 hours 59 minutes
-*@?
Time signal OFF time 0.00 0 to 99 hours 59 minutes
'A+(
Select an external
operation
OFF ON: external operation /OFF: internal operation
":@8
Lock the key OFF ON/OFF
Vista de página 12
1 2 ... 8 9 10 11 12 13 14 15 16

Comentários a estes Manuais

Sem comentários